XSDFW-40.5 high-voltage cable branch box
The XSDFW-40.5 cable branching box is used in 40.5kV three-phase AC 50Hz power distribution systems to connect cables and receive and distribute electrical energy.
Category:
Keyword:
Phone
Details
Product Description
The XSDFW-40.5 cable branching box is used in 40.5kV three-phase AC 50Hz power distribution systems to connect cables and receive and distribute electrical energy. The product has no exposed conductive parts; all conductive parts are enclosed with high-insulation-strength gel epoxy resin or silicone rubber, ensuring safety and reliability. The exterior is touchable, eliminating the risk of electric shock.
Cables are connected through elbow plugs, and power is distributed through wall bushings. The cable branching box's input and output lines can accommodate power cables with cross-sections of 50~300mm2. This product offers various installation methods, including single and double cable input/output lines. It's easy to install and maintain, poses no fire hazard, and is especially suitable for industrial and mining enterprises, high-voltage power transmission, and power distribution. It is a new type of power distribution equipment suitable for cable power transmission and distribution.
This product references the relevant provisions of GB/T11022-2020 "Common Technical Conditions for High-Voltage Switchgear and Control Equipment" and GB/T3906-2020 "3.6-40.5kV AC Metal-Enclosed Switchgear and Control Equipment".
Technical Advantages
1. All energized parts of the input and output lines are completely enclosed by high-insulation-strength gel epoxy resin or silicone rubber. The insulation layer can withstand the entire test voltage and is available in touchable and non-touchable exterior types.
1.2.8 This product references the relevant provisions of GB/T11022-2020 "Common Technical Conditions for High-Voltage Switchgear and Control Equipment" and GB/T3906-2020 "3.6-40.5kV AC Metal-Enclosed Switchgear and Control Equipment".
Technical Parameters
|
Parameter Name |
Unit |
Parameter |
|
Rated Voltage |
kV |
40.5 |
|
Rated Frequency |
Hz |
50 |
|
Rated Current of Main Busbar |
A |
630/1250 |
|
Short-Time Withstand Current of Main Busbar |
kA/s |
20/31.5kA/4s |
|
Peak Withstand Current of Main Busbar |
kA |
50 |
|
1min Power Frequency Withstand Voltage |
kV |
95 |
|
Lightning Impulse Withstand Voltage |
kV |
185 |
|
Secondary Circuit 1min Power Frequency Withstand Voltage |
kV |
2 |
|
Protection Level |
|
IP44 |
Previous
Next
Related Products
Online
Message
If you have any suggestions or feedback for our company, please fill in the relevant information on this page and submit it. A staff member will contact you in a timely manner, or please call us directly.