MVnex smart medium-voltage switchgear
MVnex-12 armored withdrawable AC metal-enclosed switchgear (hereinafter referred to as switchgear) is suitable for indoor three-phase 50/60Hz, rated voltage 3.6~12kV power systems, used for receiving and distributing three-phase AC power and automatically closing and controlling the operating circuit, disconnecting fault (including overload, short circuit, overvoltage and other faults) protection, monitoring and event recording.
Keyword:
Phone
Details
Product Description
The MVnex-12 armored withdrawable AC metal-enclosed switchgear (hereinafter referred to as switchgear) is suitable for indoor three-phase 50/60Hz power systems with rated voltage of 3.6~12kV. It is used to receive and distribute three-phase AC power, and to automatically control the operation circuit, disconnect fault (including overload, short circuit, overvoltage, etc.), protection, monitoring and event recording; widely used in power plants, substations, metallurgy and chemical industry, rail transit, factories and mines, residential areas, high-rise buildings and other various places.
The design and manufacture of the switchgear fully comply with GB/T 3906 "3.6kV~40.5kV AC metal-enclosed switchgear and control equipment" and DL/T 404 3.6kV~40.5kV "AC metal-enclosed switchgear and control equipment", GB/T 11022 "Common technical requirements for high-voltage switchgear and control equipment" and DL/T 593 "Common technical requirements for high-voltage switchgear and control equipment" standards.
Technical Advantages
1. High technical parameters: Short-time withstand current can reach 12kV, 4000A-40kA; Seismic resistance grade can reach: (AG3) 8 degrees; Grounding switch short-time withstand high: 40kA/4s; Internal arc resistance grade can reach 40kA/1s;
2. It has circuit breaker cabinets, contactor cabinets and other special cabinet types; HVX solid-sealed pole vacuum circuit breakers and CVX solid-sealed pole vacuum contactors can be installed.
Technical Parameters
|
Parameter Name |
Unit |
Technical Data |
|
|
Rated Voltage |
kV |
10 |
|
|
Maximum Operating Voltage |
kV |
12 |
|
|
Rated Insulation Level |
1min Power Frequency Withstand Voltage |
kV |
Phase-to-phase and phase-to-ground 42/Open 48 |
|
Lightning Impulse Withstand Voltage |
kV |
Phase-to-phase and phase-to-ground 75/Open 85 |
|
|
Rated Frequency |
Hz |
50 |
|
|
Rated Current |
kA |
630、1250、2500、3150、4000 |
|
|
4s Short-Time Withstand Current |
kA |
20、25、31.5、40 |
|
|
Rated Peak Withstand Current |
kA |
50、63、80、100 |
|
|
Protection Level |
|
The enclosure can reach IP41, and the circuit breaker compartment door open reaches IP2X |
|
|
Partial Discharge |
pC |
13.2kV ≤20pC |
|