MVnex smart medium-voltage switchgear

MVnex-12 armored withdrawable AC metal-enclosed switchgear (hereinafter referred to as switchgear) is suitable for indoor three-phase 50/60Hz, rated voltage 3.6~12kV power systems, used for receiving and distributing three-phase AC power and automatically closing and controlling the operating circuit, disconnecting fault (including overload, short circuit, overvoltage and other faults) protection, monitoring and event recording.

Keyword:

Phone

Details

Product Description


  The MVnex-12 armored withdrawable AC metal-enclosed switchgear (hereinafter referred to as switchgear) is suitable for indoor three-phase 50/60Hz power systems with rated voltage of 3.6~12kV. It is used to receive and distribute three-phase AC power, and to automatically control the operation circuit, disconnect fault (including overload, short circuit, overvoltage, etc.), protection, monitoring and event recording; widely used in power plants, substations, metallurgy and chemical industry, rail transit, factories and mines, residential areas, high-rise buildings and other various places.

  The design and manufacture of the switchgear fully comply with GB/T 3906 "3.6kV~40.5kV AC metal-enclosed switchgear and control equipment" and DL/T 404 3.6kV~40.5kV "AC metal-enclosed switchgear and control equipment", GB/T 11022 "Common technical requirements for high-voltage switchgear and control equipment" and DL/T 593 "Common technical requirements for high-voltage switchgear and control equipment" standards.

Technical Advantages


  1. High technical parameters: Short-time withstand current can reach 12kV, 4000A-40kA; Seismic resistance grade can reach: (AG3) 8 degrees; Grounding switch short-time withstand high: 40kA/4s; Internal arc resistance grade can reach 40kA/1s;

  2. It has circuit breaker cabinets, contactor cabinets and other special cabinet types; HVX solid-sealed pole vacuum circuit breakers and CVX solid-sealed pole vacuum contactors can be installed.

Technical Parameters


Parameter Name

Unit

Technical Data

Rated Voltage

kV

10

Maximum Operating Voltage

kV

12

Rated Insulation Level

1min Power Frequency Withstand Voltage

kV

Phase-to-phase and phase-to-ground 42/Open 48

Lightning Impulse Withstand Voltage

kV

Phase-to-phase and phase-to-ground 75/Open 85

Rated Frequency

Hz

50

Rated Current

kA

630、1250、2500、3150、4000

4s Short-Time Withstand Current

kA

20、25、31.5、40

Rated Peak Withstand Current

kA

50、63、80、100

Protection Level

 

The enclosure can reach IP41, and the circuit breaker compartment door open reaches IP2X

Partial Discharge

pC

13.2kV ≤20pC