GCS low-voltage switchgear
The GCS withdrawable low-voltage switchgear is developed by SHARESUN Electric after referring to and comprehensively improving the withdrawable low-voltage switchgear of domestic and foreign companies. It is currently one of the better low-voltage withdrawable switchgears in China. It is suitable for AC 50 (60) Hz, rated operating voltage 400V, rated current 6300A and below three-phase five-wire power supply systems.
Category:
Keyword:
Smart power distribution series
Power distribution box series
Phone
Details
Product Description
The GCS withdrawable low-voltage switchgear is developed by SHARESUN Electric after referring to and comprehensively improving the withdrawable low-voltage switchgear of domestic and foreign companies. It is currently one of the better low-voltage withdrawable switchgears in China. It is suitable for AC 50 (60) Hz, rated operating voltage 400V, rated current 6300A and below three-phase five-wire power supply systems. It can be used in power plants, substations, industrial and mining enterprises, large buildings and hotels, airports, docks, and communication centers such as radio and television as control for power generation, transmission and distribution, power conversion, and power consumption equipment, and performs reactive power compensation on its main busbars through a capacitor compensation cabinet.
This product conforms to GB/T 7251.1-2023 Low-voltage switchgear and controlgear - Part 1: General rules and GB/T 7251.2-2023 Low-voltage switchgear and controlgear - Part 2: Assemblies of power switches and control devices.
Technical Advantages
1. The low-voltage switchgear independently developed by the company has achieved standardized and modular technical solutions in its structural design and copper bar design; this product is composed of standardized and series-produced modules, and the drawers have reliable mechanical interlocking devices, making it safer and more reliable for users.
2. Various switchgears strictly follow the principles of reasonable heat dissipation channel design, normative current-carrying capacity selection, scientific eddy current and electromagnetic field design, ensuring the long-term safe and reliable operation of the switchgear;
3. Using digital factory brand technology, technical drawings and related technical information of the project can be downloaded by scanning the digital QR code on the lintel, which facilitates customer access.
Technical Parameters
|
Serial Number |
Parameter Name |
Technical Parameters |
|
|
1 |
Rated Operating Voltage (V) |
400 |
|
|
2 |
Rated Insulation Voltage (V) |
690 |
|
|
3 |
Rated Frequency (Hz) |
50(60) |
|
|
4 |
Main Busbar |
Rated Current (A) |
630-6300 |
|
5 |
Rated Short-Time Withstand Current (kA/1s) |
30/50/80/100 |
|
|
6 |
Rated Peak Withstand Current (kA) |
63/105/176/220 |
|
|
7 |
Distribution Busbar |
Rated Current (A) |
100-1400 |
|
8 |
Rated Short-Time Withstand Current (kA/1s) |
15/30/50/80 |
|
|
9 |
Rated Peak Withstand Current (kA) |
30/63/105/176 |
|
|
10 |
Protection Level |
IP40、IP30 |
|