HXGN-12 indoor metal-enclosed ring network switchgear

Indoor AC metal-enclosed ring network switchgear is suitable for indoor three-phase 50/60Hz power systems with a rated voltage of 7.2~12kV. It is used to receive and distribute three-phase AC power and to automatically close and cut off faulty circuits.

Keyword:

Smart power distribution series

Phone

Details

Product Description


  Indoor AC metal-enclosed ring main unit switchgear is suitable for indoor three-phase 50/60Hz, rated voltage 7.2~12kV power systems. It is used to receive and distribute three-phase AC power and to automatically control the switching of operating circuits, protect against faults (including overload, short circuit, overvoltage, etc.), monitor, and record events. This product is characterized by its small size, light weight, simple operation, safe use, and easy maintenance; it is widely used in urban power grid construction and renovation projects, industrial and mining enterprises, high-rise buildings, and public facilities, as a ring main power supply unit and terminal equipment, and can also be installed in prefabricated substations.

  The design and manufacture of HXGN-12 ring main units fully comply with GB/T 3096 "3.6kV-40.5kV AC metal-enclosed switchgear and control equipment", GB/T 3804 "3.6kV-40.5kV high-voltage AC load switches", GB/T 1985 "High-voltage AC isolating switches and earthing switches", GB16926 "High-voltage AC load switch-fuse combination electrical appliance", GB/T1984 "High-voltage AC circuit breaker", DL/T 404 "3.6kV-40.5kV AC metal-enclosed switchgear and control equipment".

Technical Advantages


  1. The cabinet shell is a metal-enclosed high-voltage switchgear assembled from reinforced profiles independently developed by the company;

  2. This equipment has strong completeness, small size, no risk of combustion or explosion, and reliable "five-proof" function;

  3. This product can have load switch units, load switch and fuse combination electrical appliance units, and circuit breaker units, and various design schemes can be selected according to user needs;

  4. It can be designed for application in plateau areas with an altitude of 4500m or less.

Technical Parameters


Serial Number

Item

Unit

Load Switch Unit

Combination Electrical Appliance Unit

Circuit Breaker Unit

1

Rated Voltage

kV

12

12

12

2

Rated Frequency

Hz

50

50

50

3

Rated Current

A

630

200 (depends on fuse current)

1250

4

Rated Insulation Level

1min power frequency withstand voltage

Phase-to-phase, phase-to-ground

kV

42

42

42

Break

48

48

48

Control and auxiliary circuit

2

2

2

Lightning impulse withstand voltage

Phase-to-phase, phase-to-ground

75

75

75

Break

85

85

85

5

Rated short-time withstand current

kA/s

20/4

--

31.5/4

6

Rated peak withstand current

kA

63

--

80

7

Rated short-circuit closing current

kA

50

Limited by high-voltage fuse

80

8

Rated short-circuit breaking current

kA

--

Limited by high-voltage fuse

31.5

9

Rated transfer current

A

--

1700/1400

--

10

Mechanical Life

Circuit Breaker

Times

10000

10000

10000

Load Switch

2000

2000

--

Isolating Switch

2000

2000

--

Earthing Switch

2000

2000

1000

12

IP Protection Level

Enclosure

 

IP41

IP41

IP4X